With GUIDED WAVE RADAR LEVEL TRANSMITTER you can measure all kinds of liquids essentially maintenance free. The sensor delivers precise and reliable measured values even in applications with steam, buildup, foam generation or condensation. GUIDED WAVE RADAR LEVEL TRANSMITTER is a truly cost-effective level and interface sensor for your measuring task.

  • Specification
Parameter Typical Specification
Measurement Principle Guided Wave Radar (TDR)
Measured Variable Liquid level, interface level, solids level
Measuring Range 0.3 m to 40 m (depending on probe type)
Accuracy ±2 mm to ±5 mm
Repeatability ±1 mm
Output Signal 4–20 mA with HART
Communication Protocols HART, Foundation Fieldbus, Profibus PA, Modbus (model dependent)
Power Supply 12–42 V DC
Process Temperature −196°C to +450°C (model dependent)
Process Pressure Vacuum to 400 bar (model dependent)
Dielectric Constant Requirement Typically ≥ 1.4
Probe Types Single rod, twin rod, cable, coaxial
Process Connections Threaded (NPT/BSP), Flanged, Hygienic fittings
Wetted Materials SS316L, Hastelloy C, PTFE-coated options
Housing Material Aluminum or Stainless Steel
Display Optional LCD display with local programming
Enclosure Rating IP66/IP67, NEMA 4X
Hazardous Area Approvals ATEX, IECEx, FM, CSA
Ambient Temperature −40°C to +80°C
EMC Compliance IEC 61326
Functional Safety SIL 2 / SIL 3 capable (depending on model)